产品详情
  • 产品名称:Reserve Capacity Relief Valve (RCRV) Low Temperature Storage

  • 产品型号:Reserve Capacity Relief Valve (RCRV) Low Temperatu
  • 产品厂商:其它品牌
  • 产品文档:
你添加了1件商品 查看购物车
简单介绍:
Reserve Capacity Relief Valve (RCRV) Low Temperature Storage 旨在提供有关低压,低温贮藏时,大量的水汽条件是不寻常的坦克产生超压保护。O形圈座椅提供气密性能设定压力的95%。在设定压力进行**开放 - 没有超压要求达到额定容量。
详情介绍:
Reserve Capacity Relief Valve (RCRV) Low Temperature Storage
旨在提供有关低压,低温贮藏时,大量的水汽条件是不寻常的坦克产生超压保护。O形圈座椅提供气密性能设定压力的95%。在设定压力进行**开放 - 没有超压要求达到额定容量。


Reserve Capacity Relief Valve (RCRV) Low Temperature Storage

  • Description
  • Specifications
  • Documentation
Anderson Greenwood Pressure Relief Valves, Tank Protection, Reserved Capacity Relief Valves, Anderson Greenwood Reserve Capacity Relief Valve (RCRV) Low Temperature Storage 

Designed to provide overpressure protection on low pressure, low temperature storage tanks when a large volume of vapor is generated by unusual conditions. O-ring seat provides bubble-tight performance to 95% of set pressure. Full open at set pressure – no overpressure required to achieve rated capacity.

Features & Benefits:

  • Soft Seat – An O-ring seat provides bubble-tight performance to 95% of set.
  • Tension Link – The valve is held closed by a combination of tension link and spring force, to provide positive opening at set and bubble tight shut-off at reseat.
  • Full Open at Pop – No overpressure required for rated capacity.
  • Maintenance – All parts requiring maintenance can be replaced with the valve installed, with the tank pressure at 50% or less of set.
Specifications

Sizes: 24" and 36"

Flange Mounting:
24" = 150 # Class/ANSI 16.5
36" = 25 # Class/ANSI 16.1

Reseat: Reseat pressure is 50% of set

Available set pressure range:
24" – 1.5 to 5.0 psig [103 to 345 mbarg]
36" – 1.5 to 3.0 psig [103 to 207 mbarg]

Applications
Overfill: Under some level control failure conditions, cold liquid could be pumped over the top of the inner wall and into the warm insulation space, thus generating excessive vapor. The RCRV is capable of relieving this excessive vapor.

Mechanical Failure: Should the inner wall on a double wall tank fail and permit liquid to pass through into the insulation space, excessive vapor will be rapidly generated. The RCRV can relieve the resulting vapor.

Rollover: The RCRV provides the very large orifice area needed to prevent excessive overpressure caused by boil off of lower density product rolling up and over higher density product.

Loading Error: Loading propane into a partially filled butane tank will produce dangerous quantities of vapor. The RCRV can provide the large capacity necessary to relieve this excessive vapor.


 
* 请输入您的名字,方便我们和您联系
* 请输入您的电话,方便客服及时解答您的问题
* 请输入您详情地址,方便详细提供当地的市场讯息